Seismic Installation and Code Requirements

Tested and Trusted Seismic Solutions

IBC Requirements

Purpose of Installation Requirements for Suspended Ceilings

  • Suspension systems strong enough to resist lateral forces imposed upon it without failing
  • Prevent border panels from falling from the ceiling plane
IBC Category IBC Installation Requirements
A, B

Ceiling installation should conform to basic minimums established in ASTM C636.

C

Installed to ASTM E580 Seismic Design Category C

Minimum 7/8" wall molding

Suspension system must not be attached to the wall molding

Minimum 3/8" clearance on all sides

Minimum 3/8" overlap of the suspension system on the wall molding

Ends of main beams and cross tees must be tied together to prevent their spreading

Safety wires required on light fixtures

D, E, F

Installed to ASTM C636 and ASTM E580

Minimum 2" wall molding

Suspension system must be attached to two adjacent walls – opposite walls must have a 3/4" clearance

Ends of main beams and cross tees must be tied together to prevent their spreading

Heavy-duty suspension system

Ceiling areas over 1,000 SF must have horizontal restraint wire or rigid bracing

P